Air and Water-Resistive Barrier Assemblies
Air and Water-Resistive barrier assemblies are divided into building assemblies for walls, roofs and foundations. These broad heading, in some cases, are then sub-divided into specific types of walls, roofs and foundations. Air and Water-Resistive barrier assemblies are made up of air and water-resistive barrier materials and connected with air and water-resistive barrier accessories.
Wall Assembly Evaluation – Air Barrier
ABAA has set a maximum air leakage rate for wall air barrier assemblies as being 0.04 CFM/ft2 at a pressure difference of 1.57 lb./ft2 [0.20 L/(s·m2) at a pressure difference of 75 Pa] when tested in accordance with ASTM E 2357 Standard Test Method for Determining Air Leakage of Air Barrier Assemblies.
Scope of Evaluation
ABAA evaluations establish that the assembly tested passed a specified test. Such evaluation does not constitute a product warranty and provides no prediction of useful life or future performance.
Get your air and water-resistive barrier material evaluated and listed with ABAA.
ABAA Evaluated Air and Water-Resistive Barrier Assemblies
Self Adhered Sheet Membranes
Test Results | ||||
---|---|---|---|---|
Air Leakage Rate of Wall Assembly (ASTM E2357) | Air Leakage Rate of Material (ASTM E2178) | Water Vapor Permeance (ASTM E96 – desiccant method) | Water Vapor Permeance (ASTM E96 – water method) | Details & Specs |
Air Barrier Construction Design Details
Air Barrier Master Specification |
Fluid Applied Membranes
Dow Performance Silicones www.buildabetterbarrier.com
DEFENDAIR™ 200C Air and Weather Barrier Coating
Test Results | ||||
---|---|---|---|---|
Air Leakage Rate of Wall Assembly (ASTM E2357) | Air Leakage Rate of Material (ASTM E2178) | Water Vapor Permeance (ASTM E96 – desiccant method) | Water Vapor Permeance (ASTM E96 – water method) | Details & Specs |
0.0117 L/(s·m²) @ 75 Pa [0.0023 cfm/ft² @ 1.57 psf] @ 36 mils wet |
0.0011 L/(s·m²) @ 75 Pa [0.0002 cfm/ft² @ 1.57 psf] @ 13 mils |
402 ng/Pa·s·m² [7.028 US Perms] @ 18 mils | 1,660 ng/Pa·s·m² [29.023 US Perms] @ 18 mils | Air Barrier Construction Design Details |
Gardner-Gibsonwww.gardner-gibson.com
AP-650-VP
Test Results | ||||
---|---|---|---|---|
Air Leakage Rate of Wall Assembly (ASTM E2357) | Air Leakage Rate of Material (ASTM E2178) | Water Vapor Permeance (ASTM E96 – desiccant method) | Water Vapor Permeance (ASTM E96 – water method) | Details & Specs |
0.010 L/(s·m²) @ 75 Pa [0.0020 cfm/ft² @ 1.57 psf] @ 24 mils wet |
0.0004 L/(s·m²) @ 75 Pa [0.00005 cfm/ft² @ 1.57 psf] @ 24 mils dry |
80.0 ng/Pa·s·m² [1.4 US Perms] @ 20 mils | 2000.0 ng/Pa·s·m² [35 US Perms] @ 20 mils | Air Barrier Construction Design Details |
Siplast www.siplast.com
WALLcontrolTM Modified Silicone (STPE) VP Liquid AWB
Test Results | ||||
---|---|---|---|---|
Air Leakage Rate of Wall Assembly (ASTM E2357) | Air Leakage Rate of Material (ASTM E2178) | Water Vapor Permeance (ASTM E96 – desiccant method) | Water Vapor Permeance (ASTM E96 – water method) | Details & Specs |
0.0050 L/(s·m²) @ 75 Pa [0.0010 cfm/ft² @ 1.57 psf] |
0.0002 L/(s·m²) @ 75 Pa [0.00004 cfm/ft² @ 1.57 psf] |
506 ng/Pa·s·m² [8.858 US Perms] | 871 ng/Pa·s·m² [15.242 US Perms] | Air Barrier Construction Design Details |
Sprayed Polyurethane Foam (Medium Density Closed Cell)
Barnhardt Manufacturing Company dba NCFI Polyurethaneswww.ncfi.com
InsulStar®SmartSPF & InsulBloc®SmartSPF
Test Results | ||||
---|---|---|---|---|
Air Leakage Rate of Wall Assembly (ASTM E2357) | Air Leakage Rate of Material (ASTM E2178) | Water Vapor Permeance (ASTM E96 – desiccant method) | Water Vapor Permeance (ASTM E96 – water method) | Details & Specs |
0.0437 L/(s • m2) @ 75 Pa [0.00874 cfm /ft2 @ 1.57 psf] @ 25mm [2.0″] |
0.000002 L/(s • m2) @ 75 Pa [0.0000004 cfm /ft2 @ 1.57 psf] @ 25mm [1.0″] | ng / Pa•s•m2 [0.65 US Perms] @ 50mm [2.0″] | ng / Pa•s•m2 [1.1 US Perms] @ 50mm [2.0″] | Air Barrier Construction Design Details |
BASFwww.spf.basf.com
WALLTITE® LWP
Test Results | ||||
---|---|---|---|---|
Air Leakage Rate of Wall Assembly (ASTM E2357) | Air Leakage Rate of Material (ASTM E2178) | Water Vapor Permeance (ASTM E96 – desiccant method) | Water Vapor Permeance (ASTM E96 – water method) | Details & Specs |
< 0.001 L/(s • m2) @ 75 Pa [0.0002 cfm /ft2 @ 1.57 psf] @ 25mm [1.0″] |
0.002 L/(s • m2) @ 75 Pa [0.0004 cfm /ft2 @ 1.57 psf] @ 25mm [1.0″] | 76.69ng / Pa•s•m2 [1.34 US Perms] @ 50mm [2.0″] | 93.73 ng / Pa•s•m2 [1.64 US Perms] @ 50mm [2.0″] | Air Barrier Construction Design Details |
Carlisle Spray Foam Insulationwww.carlislesfi.com
SealTite PRO HFO
Test Results | ||||
---|---|---|---|---|
Air Leakage Rate of Wall Assembly (ASTM E2357) | Air Leakage Rate of Material (ASTM E2178) | Water Vapor Permeance (ASTM E96 – desiccant method) | Water Vapor Permeance (ASTM E96 – water method) | Details & Specs |
0.0020 L/(s·m²) @ 75 Pa [0.0004 cfm/ft² @ 1.57 psf] |
0.01129 L/(s·m²) @ 75 Pa [0.0021 cfm/ft² @ 1.57 psf] @ 25.4mm |
62.935 ng/Pa·s·m² [1.6 US Perms] @ 50.8mm | 91.541 ng/Pa·s·m² [0.03 US Perms] | Air Barrier Construction Design Details |
Elastochemwww.elastochem.com
Insulthane® Extreme
Test Results | ||||
---|---|---|---|---|
Air Leakage Rate of Wall Assembly (ASTM E2357) | Air Leakage Rate of Material (ASTM E2178) | Water Vapor Permeance (ASTM E96 – desiccant method) | Water Vapor Permeance (ASTM E96 – water method) | Details & Specs |
0.001 L/(s • m2) @ 75 Pa [0.0002 cfm /ft2 @ 1.57 psf] |
0.002 L/(s • m2) @ 75 Pa [0.0004 cfm /ft2 @ 1.57 psf] | 40 ng / Pa•s•m2 [0.68 US Perms] @ 50mm [2.0″] | 36 ng / Pa•s•m2 [0.40 US Perms] @ 50mm [2.0″] | Coming Soon |
Xcelus Building Systems Incwww.xcelusbuildingsystems.com
XLS 2000
Test Results | ||||
---|---|---|---|---|
Air Leakage Rate of Wall Assembly (ASTM E2357) | Air Leakage Rate of Material (ASTM E2178) | Water Vapor Permeance (ASTM E96 – desiccant method) | Water Vapor Permeance (ASTM E96 – water method) | Details & Specs |
0.0096 L/(s • m2) @ 75 Pa [0.0002 cfm /ft2 @ 1.57 psf] |
0.0019 L/(s • m2) @ 75 Pa [0.0004 cfm /ft2 @ 1.57 psf] | 39 ng / Pa•s•m2 [0.68 US Perms] @ 50mm [2.0″] | 35.72 ng / Pa•s•m2 [0.40 US Perms] @ 50mm [2.0″] | Coming Soon |
If you have any questions about Evaluated Air and Water-Resistive Barrier Assemblies please contact the ABAA office by email at abaa@airbarrier.org or by phone at 866-956-5888.